Electric Fireplace Legionella Outbreak: 21 Cases Explained

Electric Fireplace Legionella Outbreak: 21 Cases Explained

The fireplace that caused a Legionnaires’ outbreak: why decorative mist devices belong in your risk assessment

As a company that works across both fire safety and water hygiene, this one caught our eye. A study published this year by public health officials in Tokyo traced an outbreak of Legionnaires’ disease to an unlikely source: an electric fireplace installed as decoration in a restaurant. There were no flames involved. The risk came from the water used to create them.

What happened

Between 30 September and 30 November 2024, 43 cases of Legionnaires’ disease were reported to public health centres in the Tama area of Tokyo. At first, investigators could find no obvious cluster. The patients did not live in the same place and there was no clear shared exposure.

Detailed interviews changed that. Several patients had eaten at the same restaurant, which had an electric fireplace as part of its interior design. Rather than burning anything, the fireplace created its flame effect from water vapour, using a mechanism similar to an ultrasonic mist generator.

What investigators found

Water samples taken from the fireplace’s vapour tray contained Legionella pneumophila serogroup 1 and Legionella feeleii serogroup 1 at a combined level of 3 million CFU per 100 mL.

To put that in context, HSE guidance for hot and cold water systems in the UK treats counts above 1,000 CFU per litre as a serious result requiring immediate action. The fireplace water held the equivalent of around 30 million CFU per litre.

Genetic testing then confirmed the link. Bacteria from the fireplace and bacteria from patients’ samples were indistinguishable, and all belonged to the same sequence type. In total, 21 people developed Legionnaires’ disease after visiting the restaurant, with no other activity in common and matching genetic results. The researchers concluded that the outbreak was caused by aerosols produced by the fireplace.

The authors believe this is the first reported Legionnaires’ outbreak linked to an electric fireplace in Japan. They credit fast tracing, on-site inspection and prompt guidance to the business with preventing further cases, and they call for ongoing education about how products like this should be cleaned and managed.

Why this matters

Legionnaires’ disease is caught by breathing in fine droplets of contaminated water. Ultrasonic devices do not boil water: they break it into a mist of tiny droplets, exactly the size that can be drawn deep into the lungs. Add a reservoir of standing water at room temperature, sometimes warmed further by the unit’s own lighting or heating elements, and you have conditions in which Legionella can multiply and then be released straight into the air people are breathing.

Water vapour fires and flame-effect units are increasingly popular in UK restaurants, pubs, hotels, care homes, holiday lets and homes. The same principle applies to ultrasonic humidifiers, misting systems, decorative water features and some aroma diffusers. Because they are bought as décor rather than plant, they are easily left out of water hygiene arrangements altogether.

What the law expects

Under the Health and Safety at Work etc. Act 1974, COSHH and the Approved Code of Practice L8, employers and those in control of premises must identify and assess the risk from any water system that can create an aerosol, then put suitable controls in place. L8 is not limited to cooling towers and large hot water systems. If a device holds water and releases it as a spray or mist, it should be on your Legionella risk assessment.

Practical steps for dutyholders

  • Find them. Walk your premises and list every device that stores water and produces mist or spray, including décor and seasonal items.
  • Add them to your risk assessment. Each one should be assessed, with control measures and responsibilities recorded.
  • Follow the manufacturer’s instructions, but don’t stop there. Using the recommended water type is important, but filtered or bottled water is not sterile, and bacteria can still colonise a reservoir that is not cleaned.
  • Empty, clean and dry reservoirs regularly. Never simply top up old water.
  • Drain units that are not in use, for example on closed days or out of season.
  • Keep records of cleaning and checks in your water hygiene logbook.
  • Think about who is exposed. Where older or vulnerable people are present, consider whether the feature is needed at all.

How LFS can help

Our Legionella risk assessments look beyond the obvious to every system on your premises that could put people at risk, including the ones that were only ever meant to look good. If you have water vapour fires, misting units or similar equipment on site, or you are unsure whether your current risk assessment covers them, get in touch with our team.

0800 080 3045

info@legionellaandfiresafe.co.uk

 

 

Source: Kuwahata Y, et al. Legionnaires’ disease outbreak caused by an electric fireplace-like interior product generating ultrasonic aerosols. Nihon Koshu Eisei Zasshi, 2026. View on PubMed

MOST RECENT

Fire door compliance inspection: a closed fire door with a Fire Door Keep Shut sign in a UK corridor

Fire Door Compliance: 4 Duties You Cannot Ignore

Fire door compliance is one of the clearest duties facing anyone responsible for premises, yet fire doors rarely get a second thought until something goes...
Fire extinguisher beside a fire safety checklist

Fire Safety Enforcement Is Rising: Why Your Fire Risk Assessment Matters More Than Ever

Fire safety enforcement in England is rising, with prohibition notices up 27%. Find out why a current fire risk assessment is your best protection.
Fire door in a shared hallway of a house in multiple occupation.

HMO Fire Door Failings: Lessons From the £15,000 Barrow Fine

No Fire Doors, No Alarm, No Licence: What the £15,000 Barrow HMO Fine Means for Landlords Missing HMO fire doors were among several safety failings...